Safety
Information
Introduction
Product
information
System
design
Mechanical
installation
Electrical
installation
Getting
started
Optimisation
Parameters
Technical
data
Component
sizing
Diagnostics
Unidrive SP Regen Installation Guide
141
Issue Number: 2 www.controltechniques.com
Indicates the level of the motorised pot prior to scaling. If Pr
9.21
is set to 0 or 2 this parameter is set to 0 at power-up, otherwise it retains its value at
the last power-down.
9.01
Logic function 1 output
9.02
Logic function 2 output
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
Update rate
4ms x number of menu 9 or 12 functions active
9.03
Motorised pot output
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
2
1
1
1
1
Range
Regen
±100.00 %
Update rate
4ms x number of menu 9 or 12 functions active
9.04
Logic function 1 source 1
9.14
Logic function 2 source 1
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
2
1
1
1
1
Range
Regen
Pr
0.00
to Pr
21.51
Default
Regen
Pr
0.00
Update rate
Background
9.05
Logic function 1 source 1 invert
9.15
Logic function 2 source 1 invert
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Default
Regen
0
Update rate
4ms x number of menu 9 or 12 functions active
9.06
Logic function 1 source 2
9.16
Logic function 2 source 2
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
2
1
1
1
1
Range
Regen
Pr
0.00
to Pr
21.51
Default
Regen
Pr
0.00
Update rate
Background
9.07
Logic function 1 source 2 invert
9.17
Logic function 2 source 2 invert
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Default
Regen
0
Update rate
4ms x number of menu 9 or 12 functions active
Summary of Contents for SP1201
Page 219: ......
Page 220: ...0471 0029 02 ...