Unidrive SP Regen Installation Guide
www.controltechniques.com Issue Number: 2
Figure 5-4 Regen inductor type 3 dimensions
5.3.2 Switching frequency filter inductor
Table 5-4 200V SFF inductor specifications
A2
B2
C2
A1
B1
C1
H
L
D
TH
Inductor part
number
Amps
mH
Losses
W
L
mm
D
mm
H
mm
Weight
kg
Fixing centres (x * y)
mm
Fixing
mm
Fixing
type
4401-1310
9.6
0.88
10
150
90
150
4
120 x 47
8 x 18
B
4401-1311
11.0
1.50
18
150
90
150
4
120 x 47
8 x 18
4401-1312
15.5
1.10
26
150
90
150
4
120 x 47
8 x 18
4401-1313
22
0.70
33
150
90
150
4
120 x 47
8 x 18
4401-1314
31
0.50
37
190
100
180
6
130 x 54
8 x 20
4401-1315
42
0.40
38
190
120
180
10
130 x 74
8 x 20
4401-1316
56
0.30
48
190
160
180
12
130 x 184
8 x 20
4401-1317
68
0.25
58
190
160
180
12
130 x 184
8 x 20
4401-1318
80
0.20
60
190
160
180
13
130 x 184
8 x 20
4401-1319
105
0.16
78
255
160
240
16
200 x 180
10 x 20
4401-1320
130
0.13
86
255
170
240
20
200 x 90
10 x 20
4401-1321
156
0.11
92
255
180
240
22
200 x 100
10 x 20
4401-1322
192
0.088
97
255
190
240
25
200 x 100
10 x 20
4401-1323
250
0.068
119
300
180
300
37
204 x 113
10 x 20
4401-1324
312
0.055
170
300
180
300
37
204 x 113
10 x 20
4401-1325
350
0.048
162
300
190
300
49
204 x 123
10 x 20