Unidrive SP Regen Installation Guide
www.controltechniques.com Issue Number: 2
•
The Regen drive can now be enabled, the Regen drive should
display
ACT
.
•
The commissioning of the motoring drive(s) can now be carried out.
7.4 Motoring drive commissioning
7.4.1 Motoring drive enable
When the Regen drive has been successfully synchronised, Pr
3.09
on
the Regen drive will become active and digital output F1 on terminal 24
also becomes active allowing the motoring drive(s) to be enabled. If the
Regen drive trips or attempts to re-synchronise to the supply, Pr
3.09
becomes zero and the enable signal for the motoring drive(s) is
removed.
The setting of certain parameters in the motoring drive must be given
special consideration when used in a regen system.
7.4.2 Ramp Mode - Pr 2.04 (Pr 0.15)
When a motoring drive is used in a regen system, the ramp mode should
be set to
FAST
. The default setting of standard control will result in
incorrect operation.
7.4.3 Voltage Control Mode - Open loop only Pr 5.14
(Pr 0.07)
The default setting of
UR_I
does not function correctly in the motoring
drive when used in a regen system. When the system is powered up, the
motoring drive is disabled while the Regen drive synchronises to the AC
supply. The resultant delay before the motoring drive is enabled means
that the stator resistance test cannot be completed. When open loop
vector operation is required the voltage mode should be set to
UR_S
.
7.4.4 AC Supply Loss Mode - Pr 6.03
The motoring drive will not operate correctly if the AC supply loss mode
is set to
STOP
. If the AC supply is lost, the Regen drive disables the
motoring drive and prevents a controlled stop from being completed.