The -OM1 Option limits you to
reading or writing a maximum
of 32 words of data (512 bits)
during one read or write
operation. For example, you
are restricted to accessing 32
registers in the DM area with
one CALL PLCREAD or CALL
PLCWRITE command.
Addressing bits in the -OM1 Option is a little different than in the rest of the
PLC interfaces. The -OM1 Option utilizes the Host Link bit
addressing scheme which combines the
WORD
address and the
BIT
address
into one number. For the IR, SR, LR, HR, and AR areas data is accessed in
this fashion. To read a bit at word 5 bit 3, will require an address of 503,
word 11 bit 13 requires the address of 1113. For example, to access the IR
data area, word 5, bits 6 through 9, use the following command
CALL PLCREAD(0, 2, 506, 4, A)
This command accesses word 5, bit 6 and reads four bits placing the result
in variable A. Note that the four bits will be aligned in variable A with bit
506 in the 2^0 location 507 in the 2^1 location and so on. This makes bit
testing within a BASIC program very simple.
Writes to individual bit locations in the Omron PLC is performed via a read
modify write process.
EXTREME
care should be taken when using data bits
which may be updated during a scan. Host Link only allows data to be read
and written to on
WORD
boundaries. This forces the -OM1 Option to read
surrounding bits to obtain an entire word, then sets or clears the desired bits
and write the recomposed words back to the PLC. If the data the -OM1
Option reads surrounding the operation is updated during a scan,
unpredictable results may occur. Writing to outputs may be something to
avoid if your program does not continually update them. Reads do not suffer
from this problem.
READ
WRITE
Cmd
Memory Type
Range
Data / Response
•
•
1
Status Word
*
1 word
•
2
IR & SR
*
1 word per 16 bits
•
3
IR & SR
*
1 word per 16 bits
•
•
4
DM
*
1 word per register
5
N/A
*
N/A
6
N/A
*
N/A
7
N/A
*
N/A
8
N/A
*
N/A
•
•
9
LR
*
1 word per 16 bits
•
•
10
HR
*
1 word per 16 bits
•
•
11
AR
*
1 word per 16 bits
PLC Dependent
Table 12
Cross Reference
-OM1 Memory Type Vs. Call
PLCREAD / PLCWRITE
T-60 Operator's Manual
86
Summary of Contents for T-60
Page 1: ...T 60 Operator s Manual P N 400248 00 Rev A3 Date November1 1995 ...
Page 2: ......
Page 4: ...ii ...
Page 8: ...Table of Contents vii ...
Page 12: ...T 60 Operator s Manual 4 ...
Page 15: ...Figure 3 Mounting Figure 4 Mounting Clips Installation Through Panel Mounting 7 ...
Page 38: ...T 60 Operator s Manual 30 ...
Page 44: ...T 60 Operator s Manual 36 ...
Page 52: ...T 60 Operator s Manual 44 ...
Page 64: ...T 60 Operator s Manual 56 ...
Page 66: ...Figure 21 Physical Dimensions T 60 Operator s Manual 58 ...
Page 113: ...Appendix A List of Figures A 3 ...