Configuration
42
Installation, Operation, and Maintenance Manual
ES-09373-1
Configuration
August 17, 2022
8.4
Configuration Menu (Continued)
8.4.4
T OUT Menu
It is the time set in the menu for the positioner to move the valve during the
calibration process.
A failure is indicated after three consecutive errors occur in the calibration process.
Tout is factory programmed for 10 seconds, but can be adjusted from 10 to 120
seconds.
8.4.4.1
Accessing the T OUT Menu
•
Press ENTER button for 3 seconds to enter the menu.
•
Use the DOWN button to move to the T OUT option. The UP button returns to
the previous option.
•
Use the ENTER button to select the option. The display shows SURE.
•
To continue, use the ENTER button.
•
Use the ENTER button to select the digit, and the UP or DOWN buttons to
change the digit.
•
When the value is ready, confirm with the ENTER button for 3 seconds.
•
If you want to exit without any change, use the UP button for 3 seconds and
return to the main menu.
Large valves and actuators may require longer T OUT time, because it takes longer to
move the valve.
IMPORTANT
Figure 8-16 TIMEOUT Menu