The "Input Level" is defined for the different modes in the table below.
Mode
Input Level
Voltage
(Input Voltage/ 10V) x 100.00%
0-20mA
(Input Current / 20mA) x 100.00%
20-0mA
(20mA - Input Current) / 20mA x 100.00%
4-20mA
(Input Current - 4mA) / 16mA x 100.00%
20-4mA
(20mA - Input Current) / 16mA x 100.00%
Parameter
07.002
Analog Input 2
Short description
Displays the value of analog input 2
Mode
Open
‑
loop
Minimum
-100.00
Maximum
100.00
Default
Units
%
Type
16 Bit Volatile
Update Rate
4ms
Display Format
Standard
Decimal Places
2
Coding
RO, FI, ND, NC, PT
See
Analog I/O
.
Voltage mode
: This input is a unipolar voltage 0-10V.
Digital mode
: This input can also be configured as a digital input in which case this parameter will indicate 0.00% or 100.00% depending on the state of the input.
The "Input Level" is defined for the different modes in the table below.
Mode
Input Level
Voltage (Input Voltage/ 10V) x 100.00%
Digital
0.00% (corresponds to logical 0 if less than 9V) or 100.0% (corresponds to logical 1 if more than 11V)
Parameter
07.004
Stack Temperature
Short description
Displays the temperature currently being measured on the heat sink
Mode
Open
‑
loop
Minimum
-250
Maximum
250
Default
Units
°C
Type
16 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
This parameter displays the temperature currently being measured on the heat sink. This is used as part of the drive thermal model, see
Drive Over-temperature Alarm
(10.018) for further details.
Parameter
07.005
Auxiliary Temperature
Short description
Displays the temperature currently being measured on the power system
Mode
Open
‑
loop
Minimum
-250
Maximum
250
Default
Units
°C
Type
16 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
This parameter displays the temperature currently being measured on the power system on large frames. This is used as part of the drive thermal model.
Parameter
07.007
Analog Input 1 Mode
Short description
Defines the mode of analog input 1
Mode
Open
‑
loop
Minimum
-6
Maximum
6
Default
6
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
-6
4-20.S
-5
20-4.S
-4
4-20.L
-3
20-4.L
-2
4-20.H
-1
20-4.H
0
0-20
1
20-0
2
4-20.tr
3
20-4.tr
4
4-20
5
20-4
6
Volt
See
Analog Input 1
(07.001).
The table below gives all the possible analog input modes.
In 4-20mA and 20-4mA current input modes the software detects a current input less than 3mA as a current loop loss and initiates an action depending on the mode set in the table below.
102
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...