Parameter
08.025
Digital Input 05 Destination A
Short description
Defines the destination parameter for Digital Input 5
Mode
Open
‑
loop
Minimum
0.000
Maximum
30.999
Default
1.041
Units
Type
16 Bit User Save
Update Rate
Drive reset read
Display Format
Standard
Decimal Places
3
Coding
RW, DE, PT
Digital Input 05 Destination A
(08.025) provides the destination parameter if
DI5 Control
(08.085) is at its default value of 0.
Parameter
08.028
Relay 1 Output Source A
Short description
Defines the source parameter for relay 1
Mode
Open
‑
loop
Minimum
0.000
Maximum
30.999
Default
10.001
Units
Type
16 Bit User Save
Update Rate
Drive reset read
Display Format
Standard
Decimal Places
3
Coding
RW, PT
Relay 1 Output Source A
(08.028) provides the source parameter if
Relay 1 Control
(08.098) is at its default value of 0.
Parameter
08.031
Digital I/O 01 mode
Short description
Defines the mode for the functionality of digital input/output 1
Mode
Open
‑
loop
Minimum
0
Maximum
3
Default
1
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
Description
0
Input
Digital input
1
Output
Digital output
2
FR
Frequency output
3
Pulse
PWM output
This parameter selects the function of input/output DI/O 1.
See also
Digital I/O 1 State
(08.001).
Parameter
08.035
Digital input 5 mode
Short description
Defines the function for digital input 5
Mode
Open
‑
loop
Minimum
0
Maximum
4
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
Description
0
Input
Input
1
Th.Sct
Temperature measurement input with short circuit detection
(Resistance <50Ohm)
2
th
Temperature measurement input with Thermistor trip, but
without short circuit detection
3
Th.NoTr
Temperature measurement input with no trips
4
FR
Frequency Input
This parameter selects the function of input DI 05.
For digital input operation see
Digital Input 5 State
(08.005).
For operation as a thermistor input see
Thermistor Type
(07.046) and
Thermistor Feedback
(07.047).
The motor thermistor should be connected between terminal 14 and terminal 1 (0 V).
For operation as a frequency input see
Position
(03.029).
Parameter
08.041
Keypad Run Button State
Short description
Displays the state for the Keypad Run Forward button
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Digital Input 11 (Keypad Run Button), Digital Input 12 (Keypad Auxiliary Button) and Digital Input 14 (Keypad Stop Button) represent the state of the Run, Auxiliary and Stop buttons on any keypad fitted or
connected to the drive; the input state is determined by OR'ing the state of the button on each keypad connected to the drive, if the button is pressed the state parameter is one otherwise it is zero. If a keypad is
not fitted the state parameters are zero.
Parameter
08.042
Keypad Auxiliary Button State
Short description
Displays the state for the Keypad Auxilary button
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
See
Keypad Run Button State
(08.041).
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
117
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...