Timers
If the enable input to a timer is active and the repeat function is set to a non-zero value then the timer is active even if the destination is not routed to
valid a parameter. The timers are updated in the background task and have a resolution of 1s.
The following is a description of Timer 1, but Timer 2 behaves in the same way. If
Timer 1 Invert
= 0 then
Timer 1 Output
(09.042) is inactive before the
Timer 1 Start Date
(09.035) /
Timer 1 Start Time
(09.036), active between this date/time and
Timer 1 Stop Date
(09.037) /
Timer 1 Stop Time
(09.038)
and then inactive after the stop time/date within the timer 1 repeat period as shown in the diagram below.
Timer 1 Repeat Function
(09.039) defines the length of the repeat period. For example if
Timer 1 Repeat Function
(09.039) = 2 then the repeat period is
one day. The output is inactive until the time reaches the hour, minute and second defined in
Timer 1 Start Time
(09.036), and remains active until the
time reaches the hour, minute and second defined in
Timer 1 Stop Time
(09.038). Different repeat periods may be selected as given in the table below.
The table shows the constituent parts of the date and time that are used to determine the start and stop events. If the repeat period is set to every week
then
Timer 1 Start Date
(09.035) and
Timer 1 Stop Date
(09.037) define the day of the week and not the date (i.e. 00.00.00 = Sunday, 00.00.01 =
Monday, etc.). If the stop time event is set to occur at or before the start time event or the
Timer 1 Repeat Function
(09.039) = 0 or
Timer 1 Enable
(09.040) = 0 the output remains inactive at all times (i.e.
Timer 1 Output
(09.042) = 0 if
Timer 1 Invert
= 0).
128
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...