Parameter
10.013
Reverse Direction Commanded
Short description
Indicates that the reverse direction has been commanded
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Reverse Direction Commanded
(10.013) indicates the reference direction at the input to the ramp system. If the
Pre-ramp Reference
(01.003) is negative
Reverse Direction Commanded
(10.013) is one otherwise
Reverse Direction Commanded
(10.013) is zero.
Parameter
10.014
Reverse Direction Running
Short description
Indicates that the drive is running in the reverse direction
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Reverse Direction Running
(10.014) is set to one if the
Post Ramp Reference
(02.001) is negative otherwise it is set to zero.
Parameter
10.015
Supply Loss
Short description
Indicates that the drive is in the supply loss state
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Supply Loss
(10.015) indicates that the drive is in the supply loss state. This condition can only occur if supply loss detection is enabled, i.e.
Supply Loss Mode
(06.003) is set to a non-zero value. In the supply loss state the drive will attempt to stop the motor or ride through the mains loss by absorbing energy from the motor
load's rotation.
Parameter
10.016
Under Voltage Active
Short description
Indicates that the drive is in the under voltage state
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Under Voltage Active
(10.016) indicates that the drive is in the under voltage state.
Parameter
10.017
Motor Overload Alarm
Short description
Indicates that the motor overload accumulator is above 75% and the output current is high
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Motor Overload Alarm
(10.017) is set if the drive output current is higher than the defined protection level and the
Motor Protection Accumulator
(04.019) > 75%. See
Motor Thermal Time Constant 1
(04.015) and
Thermal Protection Mode
(04.016) for more details.
Parameter
10.018
Drive Over-temperature Alarm
Short description
Indicates that the drive over-temperature alarm is active
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Drive Over-temperature Alarm
(10.018) is set if
Percentage Of Drive Thermal Trip Level
(07.036) is greater than 90%.
148
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...