Parameter
10.060
Trip 9 Time
Short description
Shows the time at which trip 9 occurred
Mode
Open
‑
loop
Minimum
0
(Display: 00:00:00)
Maximum
235959
(Display: 23:59:59)
Default
Units
Type
32 Bit Power Down Save
Update Rate
Write on trip
Display Format
Time
Decimal Places
0
Coding
RO, ND, NC, PT
See
Trip 0
(10.020).
Parameter
10.061
Braking Resistor Resistance
Short description
Set to the resistance value of the braking resistor
Mode
Open
‑
loop
Minimum
0.00
Maximum
10000.00
Default
0.00
Units
Ω
Type
32 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW
See
Braking Resistor Rated Power
(10.030).
Parameter
10.064
Remote Keypad Battery Low
Short description
Indicates that the real time clock battery in the remote keypad is low
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Remote Keypad Battery Low
(10.064) is set to one when a keypad is connected to the drive user comms port with an internal real-time clock and the battery is not
fitted or the voltage is below the minimum threshold.
Parameter
10.065
Auto-tune Active
Short description
Indicates that an auto-tune sequence is active
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Auto-tune Active
(10.065) is set to one while an auto-tune sequence is active.
Parameter
10.066
Limit switch active
Short description
Indicates that a limit switch is enabled and active
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Limit switch active
(10.066) is set to one when a limit switch is enabled and active.
Parameter
10.068
Hold Drive Healthy on Under Voltage
Short description
Set to hold drive healthy if the drive is in the under voltage state
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
Hold Drive Healthy on Under Voltage
(10.068) can be used to hold the drive healthy active (
Drive Healthy
(10.001) = 1 and not flash the status LED on the front of
the drive) when the drive is in the under voltage state (
Under Voltage Active
(10.016) = 1).
If
Hold Drive Healthy on Under Voltage
(10.068) = 0 and
Under Voltage Active
(10.016) = 1, then
Drive Healthy
(10.001) will be set to 0 and the status LED on the
front of the drive will flash.
If
Hold Drive Healthy on Under Voltage
(10.068) = 1,
Under Voltage Active
(10.016) = 1 and the drive is not tripped (i.e.
Drive Status
(10.101) does not equal 9), then
Drive Healthy
(10.001) will be set to 1 and the status LED on the front of the drive will not flash.
If the drive is tripped then
Drive Healthy
(10.001) will be set to 0 and the status LED will flash independent of what
Hold Drive Healthy on Under Voltage
(10.068) is
set to.
164
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...