Parameter
01.008
Negative Reference Clamp Enable
Short description
Set to 1 to allow the minimum reference clamp value to be negative
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Minimum Speed
(01.007).
Parameter
01.009
Reference Offset Select
Short description
Enables the use of the reference offset
Mode
Open
‑
loop
Minimum
0
Maximum
2
Default
0
Units
Type
8 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Reference Offset
(01.004).
Parameter
01.010
Bipolar Reference Enable
Short description
Enables the minimum value of the reference to be negative
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Minimum Speed
(01.007).
Parameter
01.011
Reference On
Short description
Indicates that the reference from the reference system is active
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
2ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Reference On
(01.011), which is controlled by the drive sequencer (see Menu 06) indicates that the reference from the reference system is active. Note that
Reference On
(01.011) is also used to enable and disable the
Hard Frequency Reference
(03.022).
Parameter
01.012
Reverse Select
Short description
Indicates when the reverse function is active
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
2ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Reverse Select
(01.012), which is controlled by the drive sequencer (see Menu 06), is used to invert
Reference Selected
(01.001) or the
Jog Reference
(01.005).
Parameter
01.013
Jog Select
Short description
Indicates when the jog function is active
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
2ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Jog Select
(01.013) which is controlled by the drive sequencer (see Menu 06), is used to select the
Jog Reference
(01.005).
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
19
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...