Variable Selector 1 Mode
(12.010)
Variable Selector 1 Output
(12.012)
0: Input 1
Input 1
1: Input 2
Input 2
2: Add
Input 1 + Input 2
3: Subtract
Input 1 - Input 2
4: Multiply
(Input 1 x Input 2) / 100.00%
5: Divide
(Input 1 x 100.00%) / Input 2
6: Time Const
Input 1 / (1 + τs) where τ is
Variable Selector 1 Control
(12.015) in seconds
7: Ramp
Input 1 is an input to a linear ramp function where the time to ramp from 0.00% to 100.00% of the input parameter
range is defined by
Variable Selector 1 Control
(12.015) in seconds. e.g. if the input parameter is at 50% of its range,
the output value will reach 50% in 50% of the time set in
Variable Selector 1 Control
(12.015)
8: Modulus
| Input 1 |
9: Powers
If
Variable Selector 1 Control
(12.015) = 0.02 then Output = Input
2
/ 100.00%
Else if
Variable Selector 1 Control
(12.015) = 0.03 then Output = Input
3
/ (100.00%)
2
Else Output = Input 1
Parameter
12.009
Variable Selector 1 Source 2
Short description
Defines the 2nd source parameter for variable selector 1
Mode
Open
‑
loop
Minimum
0.000
Maximum
30.999
Default
0.000
Units
Type
16 Bit User Save
Update Rate
Drive reset read
Display Format
Standard
Decimal Places
3
Coding
RW, PT, BU
See
Variable Selector 1 Source 1
(12.008).
Parameter
12.010
Variable Selector 1 Mode
Short description
Defines the mode for variable selector
Mode
Open
‑
loop
Minimum
0
Maximum
9
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
See
Variable Selector 1 Source 1
(12.008).
Parameter
12.011
Variable Selector 1 Destination
Short description
Defines the destination parameter for variable selector 1
Mode
Open
‑
loop
Minimum
0.000
Maximum
30.999
Default
0.000
Units
Type
16 Bit User Save
Update Rate
Drive reset read
Display Format
Standard
Decimal Places
3
Coding
RW, DE, PT, BU
See
Variable Selector 1 Source 1
(12.008).
Parameter
12.012
Variable Selector 1 Output
Short description
Displays the output of variable selector 1
Mode
Open
‑
loop
Minimum
-100.00
Maximum
100.00
Default
Units
%
Type
16 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
2
Coding
RO, ND, NC, PT
See
Variable Selector 1 Source 1
(12.008).
Parameter
12.013
Variable Selector 1 Source 1 Scaling
Short description
Defines the scaling for the 1st input for variable selector 1
Mode
Open
‑
loop
Minimum
-4.000
Maximum
4.000
Default
1.000
Units
Type
16 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
3
Coding
RW
See
Variable Selector 1 Source 1
(12.008).
194
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...