Parameter
21.028
M2 Regenerating Current Limit
Short description
Mode
Open
‑
loop
Minimum
−VM_MOTOR2_CURRENT_LIMIT
Maximum
VM_MOTOR2_CURRENT_LIMIT
Default
165.0
Units
%
Type
16 Bit User Save
Update Rate
16ms
Display Format
Standard
Decimal Places
1
Coding
RW, VM, RA
This is the motor map 2 equivalent for
Regenerating Current Limit
(04.006).
Parameter
21.029
M2 Symmetrical Current Limit
Short description
Defines the symmetrical current limit used for motor map 2
Mode
Open
‑
loop
Minimum
−VM_MOTOR2_CURRENT_LIMIT
Maximum
VM_MOTOR2_CURRENT_LIMIT
Default
165.0
Units
%
Type
16 Bit User Save
Update Rate
16ms
Display Format
Standard
Decimal Places
1
Coding
RW, VM, RA
This is the motor map 2 equivalent for
Symmetrical Current Limit
(04.007).
Parameter
21.033
M2 Low Frequency Thermal Protection Mode
Short description
Set to enable low frequency thermal protection mod
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
This is the motor map 2 equivalent for
Low Frequency Thermal Protection Mode
(04.025).
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
227
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...