Parameter
01.029
Skip Reference 1
Short description
Defines the 1st reference point to skip
Mode
Open
‑
loop
Minimum
0.00
Maximum
550.00
Default
0.00
Units
Hz
Type
32 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW
The skip references functions are available to prevent continuous operation within a specified frequency range (i.e. where mechanical resonance may occur).
When
Skip Reference 1
(01.029) = 0 Filter 1 is disabled.
Skip Reference Band 1
(01.030) defines the range either side of
Skip Reference 1
(01.029) over which
references are rejected in either direction. The actual rejection band is therefore twice that defined by
Skip Reference Band 1
(01.030) with
Skip Reference 1
(01.029) as the centre of the band. When the selected reference is within the rejection band the lower limit of the band is passed through the filter so that
reference is always less than demanded.
Filter 2 (
Skip Reference 2
(01.031),
Skip Reference Band 2
(01.032)) and Filter 3 (
Skip Reference 3
(01.033),
Skip Reference Band 3
(01.034)) operate in the
same ways as Filter 1.
If any of the filters are active (i.e. the reference is within their rejection band)
Reference In Rejection Zone
(01.035) is set to 1, otherwise it is 0.
This parameter is unipolar, but the skip frequency operates at this frequency for both directions of rotation.
Parameter
01.030
Skip Reference Band 1
Short description
Defines the range either side of skip reference 1 to be implemented
Mode
Open
‑
loop
Minimum
0.00
Maximum
25.00
Default
0.50
Units
Hz
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW, BU
See
Skip Reference 1
(01.029).
Parameter
01.031
Skip Reference 2
Short description
Defines the 2nd reference point to skip
Mode
Open
‑
loop
Minimum
0.00
Maximum
550.00
Default
0.00
Units
Hz
Type
32 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW
See
Skip Reference 1
(01.029).
Parameter
01.032
Skip Reference Band 2
Short description
Defines the range either side of skip reference 2 to be implemented
Mode
Open
‑
loop
Minimum
0.00
Maximum
25.00
Default
0.50
Units
Hz
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW, BU
See
Skip Reference 1
(01.029).
Parameter
01.033
Skip Reference 3
Short description
Defines the 3rdreference point to skip
Mode
Open
‑
loop
Minimum
0.00
Maximum
550.00
Default
0.00
Units
Hz
Type
32 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW
See
Skip Reference 1
(01.029).
Parameter
01.034
Skip Reference Band 3
Short description
Defines the range either side of skip reference 3 to be implemented
Mode
Open
‑
loop
Minimum
0.00
Maximum
25.00
Default
0.50
Units
Hz
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW, BU
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
23
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...