Parameter
01.047
Preset Select Flag 3
Short description
Defines which preset is selected by the drive
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW, NC
See
Reference Selector
(01.014).
Parameter
01.048
Preset Selector Timer Reset
Short description
Set to 1 to hold the preset selected indicator at 1
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, NC
See
Preset Selector Timer
(01.016).
Parameter
01.049
Reference Selected Indicator
Short description
Displays which reference is currently selected
Mode
Open
‑
loop
Minimum
1
Maximum
6
Default
Units
Type
8 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
See
Reference Selector
(01.014).
Parameter
01.050
Preset Selected Indicator
Short description
Displays which preset is currently selected
Mode
Open
‑
loop
Minimum
1
Maximum
8
Default
Units
Type
8 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
See
Reference Selector
(01.014).
Parameter
01.051
Power-up Keypad Control Mode Reference
Short description
Defines which value of keypad control mode reference is displayed at power-up
Mode
Open
‑
loop
Minimum
0
Maximum
2
Default
0
Units
Type
8 Bit User Save
Update Rate
Power-up read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
Description
0
Reset
Keypad reference is zero
1
Last
Keypad reference is the last used value
2
Preset
Keypad reference is copied from Preset speed 1 (01.21)
Power-up Keypad Control Mode Reference
(01.051) defines the value written to
Keypad Control Mode Reference
(01.017) at power-up as given below.
Power-
up Keypad Control Mode Reference
(01.051)
Value wrriten to
Keypad Control Mode Reference
(01.017) at power-up
0
0.0
1
The value in
Keypad Control Mode Reference
(01.017) at the previous power-down
2
The value saved in
Preset Reference 1
(01.021)
26
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...