Deceleration Rate Select Bit 2
(02.037)
Deceleration Rate Select Bit 1
(02.036)
Deceleration Rate Select Bit 0
(02.035)
Deceleration rate
selected
0
0
0
Deceleration Rate 1
(02.021)
0
0
1
Deceleration Rate 2
(02.022)
0
1
0
Deceleration Rate 3
(02.023)
0
1
1
Deceleration Rate 4
(02.024)
1
0
0
Deceleration Rate 5
(02.025)
1
0
1
Deceleration Rate 6
(02.026)
1
1
0
Deceleration Rate 7
(02.027)
1
1
1
Deceleration Rate 8
(02.028)
Parameter
02.021
Deceleration Rate 1
Short description
Defines the deceleration rate present in deceleration rate 1
Mode
Open
‑
loop
Minimum
−VM_ACCEL_RATE
Maximum
VM_ACCEL_RATE
Default
10.0
Units
s
Type
32 Bit User Save
Update Rate
16ms
Display Format
Standard
Decimal Places
1
Coding
RW, VM
See
Ramp Rate Units
(02.039) for the definition of Ramp rate frequency
Deceleration Rate 1
(02.021) -
Deceleration Rate 8
(02.028) can be selected to define the linear ramp rate. The deceleration rate applies when the
frequency is changing towards zero.
Selecting a ramp rate that has been set to zero in Asynchronous mode disables the ramp system so that the
Post Ramp Reference
(02.001) follows the
Pre-ramp Reference
(01.003) without any delay for acceleration or deceleration. It should be noted that this also disables the standard ramp d.c. link
voltage controller and the frequency based current limits.
Parameter
02.022
Deceleration Rate 2
Short description
Defines the deceleration rate present in deceleration rate 2
Mode
Open
‑
loop
Minimum
−VM_ACCEL_RATE
Maximum
VM_ACCEL_RATE
Default
10.0
Units
s
Type
32 Bit User Save
Update Rate
16ms
Display Format
Standard
Decimal Places
1
Coding
RW, VM
See
Deceleration Rate 1
(02.021).
Parameter
02.023
Deceleration Rate 3
Short description
Defines the deceleration rate present in deceleration rate 3
Mode
Open
‑
loop
Minimum
−VM_ACCEL_RATE
Maximum
VM_ACCEL_RATE
Default
10.0
Units
s
Type
32 Bit User Save
Update Rate
16ms
Display Format
Standard
Decimal Places
1
Coding
RW, VM
See
Deceleration Rate 1
(02.021).
Parameter
02.024
Deceleration Rate 4
Short description
Defines the deceleration rate present in deceleration rate 4
Mode
Open
‑
loop
Minimum
−VM_ACCEL_RATE
Maximum
VM_ACCEL_RATE
Default
10.0
Units
s
Type
32 Bit User Save
Update Rate
16ms
Display Format
Standard
Decimal Places
1
Coding
RW, VM
See
Deceleration Rate 1
(02.021).
38
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...