4. Two banks are not provided in non-volatile media cards therefore the card could be corrupted if the power is removed when the drive is writing
data to the card.
Loading defaults
A drive reset with 1233 in
Parameter mm.000
(mm.000) loads the defaults defined for each parameter. If defaults are loaded with 1244 in
Parameter
mm.000
(mm.000) then the parameters in the table below have different defaults that are intended for the 60Hz regions.
Parameter
Default
Drive modes
Drive voltage rating
Maximum reference clamp
(01.006)
60.00Hz
All
All
Standard Ramp Voltage
(02.008)
775V
All
400V
Motor Rated Frequency
(05.006)
60.00Hz
All
All
Motor Rated Load rpm
(05.008)
1800rpm
All
All
Motor
Rated Voltage
(05.009)
460V
All
400V
M2 Maximum Reference Clamp
(21.001)
60.00Hz
All
All
M2 Motor Rated Frequency
(21.006)
60.00Hz
All
All
M2 Motor Rated Load rpm
(21.008)
1800rpm
All
All
M2 Motor Rated Voltage
(21.009)
460V
All
All
Non-volatile media card data transfer
Details of the data that can be stored on a non-volatile media card and the methods to transfer/access this data are given in Menu 11.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
5
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...