12.1.19 Weights
Table 12-9 Overall drive weights
12.1.20 SAFE TORQUE OFF data
TBA.
12.1.21 Input current, fuse and cable size ratings
The input current is affected by the supply voltage and impedance.
Typical input current
The values of typical input current are given to aid calculations for power flow and power loss.
The values of typical input current are stated for a balanced supply.
Maximum continuous input current
The values of maximum continuous input current are given to aid the selection of cables and fuses. These values are stated for the worst case
condition with the unusual combination of stiff supply with bad balance. The value stated for the maximum continuous input current would only be
seen in one of the input phases. The current in the other two phases would be significantly lower.
The values of maximum input current are stated for a supply with a 2 % negative phase-sequence imbalance and rated at the maximum supply fault
current given in Table 12-10.
Table 12-10 Supply fault current used to calculate maximum input currents
Table 12-11 AC Input current and fuse ratings (100 V)
Size
Model
kg
lb
1
All
0.75
1.65
2
1.0
2.2
3
1.5
3.3
4
3.13
6.9
Model
Symmetrical fault level (kA)
All
100
Fuses
The AC supply to the drive must be installed with suitable protection against overload and short-circuits. Table 12-11 shows the
recommended fuse ratings. Failure to observe this requirement will cause risk of fire.
Model
Typical input
current
Maximum
continuous input
current
Maximum overload
input current
Fuse rating
IEC gG
Class CC or Class J
Maximum
Maximum
A
A
A
A
A
01100017
8.7
8.7
10
10
01100024
11.1
11.1
16
16
02100042
18.8
18.8
20
20
02100056
24.0
24.0
25
25