Table 12-19 Maximum motor cable lengths (200 V drives)
Table 12-20 Maximum motor cable lengths (400 V drives)
•
Cable lengths in excess of the specified values may be used only
when special techniques are adopted; refer to the supplier of the
drive.
•
The default switching frequency is 3 kHz for Open-loop and RFC-A.
The maximum cable length is reduced from that shown in Table 12-18,
Table 12-19 and Table 12-20 if high capacitance motor cables are used.
For further information, refer to section on page 39.
200 V Nominal AC supply voltage
Model
Maximum permissible motor cable length for each of the following switching frequencies
0.667
kHz
1
kHz
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12 kHz
16 kHz
01200017
50 m
37.5
25 m
18.75
12.5 m
9 m
01200024
01200033
01200042
02200024
100 m
75 m
50 m
37.5
25 m
18 m
02200033
02200042
02200056
02200075
03200100
100 m
75 m
50 m
37.5
25 m
18 m
04200133
100 m
75 m
50 m
37.5
25 m
18 m
04200176
400 V Nominal AC supply voltage
Model
Maximum permissible motor cable length for each of the following switching frequencies
0.667
kHz
1
kHz
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
02400013
100 m
75 m
50 m
37.5
25 m
18.25 m
02400018
02400023
02400032
02400041
03400056
100 m
75 m
50 m
37.5
25 m
18.25 m
03400073
03400094
04400135
100 m
75 m
50 m
37.5
25 m
18.25 m
04400170