Unidrive M400 User Guide
185
Issue Number: 2
Power Data
Power system configuration data error
220
The
Power Data
trip indicates that there is an error in the configuration data stored in the power system.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
Power Down Save
Power down save error
37
The
Power Down Save
trip indicates that an error has been detected in the power down save parameters saved in non-
volatile memory.
Recommended actions:
•
Perform a 1001 save in Pr
mm.000
to ensure that the trip doesn’t occur the next time the drive is powered up.
PSU
Internal power supply fault
5
The
PSU
trip indicates that one or more internal power supply rails are outside limits or overloaded.
Recommended actions:
•
Remove the option module and perform a reset
•
There is a hardware fault within the drive – return the drive to the supplier
Reserved
Reserved trips
14-17
11
09
01
94 - 95
103 - 108
191 - 198
168 - 173
238 - 245
23, 39, 99, 176,
205 - 214
223 - 224
These trip numbers are reserved trip numbers for future use. These trips should not be used by the user application
programs.
Source
xx
y
zz
Description
Control
system
00
0
01
No data was obtained from the power board.
Control
system
00
0
02
There is no data table in node 1.
Control
system
00
0
03
The power system data table is bigger than the space available in
the control pod to store it.
Control
system
00
0
04
The size of the table given in the table is incorrect.
Control
system
00
0
05
Table CRC error.
Control
system
00
0
06
The version number of the generator software that produced the
table is too low.
Control
system
0
0
07
The power data table failed to be stored in the power board.
Power
system
01
0
00
The power data table used internally by the power module has an
error.
Power
system
01
0
01
The power data table that is uploaded to the control system on
power up has an error.
Power
system
01
0
02
The power data table used internally by the power module does
not match the hardware identification of the power module.
Source
xx
y
zz
Description
Control
system
00
0
00
Internal power supply overload.
Power
system
01
1
Trip Number
Description
01
Reserved resettable trip
94 -95
Reserved resettable trip
103 - 108
Reserved resettable trip
191 – 198
Reserved resettable trip
168 - 173
Reserved resettable trip
238 - 245
Reserved non-resettable trip