36
Unidrive M400 User Guide
Issue Number: 2
Table 4-3 AC Input current and fuse ratings (100 V)
Table 4-4 AC Input current and fuse ratings (200 V)
Table 4-5 AC Input current and fuse ratings (400 V)
Ensure cables used suit local wiring regulations.
Fuses
The AC supply to the drive must be installed with suitable protection against overload and short-circuits. Table 4-3, Table 4-4 and Table 4-
5 show the recommended fuse ratings. Failure to observe this requirement will cause risk of fire.
WARNING
Model
Typical input
current
A
Maximum
continuous
input current
A
Maximum
overload input
current
A
Fuse rating
IEC gG
Class CC or Class J
Maximum
A
Maximum
A
01100017
8.7
8.7
10
10
01100024
11.1
11.1
16
16
02100042
18.8
18.8
20
20
02100056
24.0
24.0
25
25
Model
Typical input
current
A
Maximum
continuous
input current
A
Maximum
overload input
current
A
Fuse rating
IEC gG
Class CC or Class J
Maximum
A
Maximum
A
1ph
3ph
1ph
3ph
01200017
4.5
4.5
6
5
01200024
5.3
5.3
10
01200033
8.3
8.3
10
01200042
10.4
10.4
16
16
02200024
5.3/3.2
5.3/4.1
6
10
5
02200033
8.3/4.3
8.3/6.7
10
10
02200042
10.4/5.4
10.4/7.5
16
10
16
10
02200056
14.9/7.4
14.9/11.3
20
16
20
16
02200075
18.1/9.1
18.1/13.5
03200100
23.9/12.8
23.9/17.7
25
20
25
20
04200133
23.7/13.5
23.7/16.9
25
20
25
20
04200176
17.0
21.3
25
25
Model
Typical input
current
A
Maximum
continuous input
current
A
Maximum
overload input
current
A
Fuse rating
IEC gG
Class CC or Class J
Maximum
A
Maximum
A
02400013
2.1
2.4
6
5
02400018
2.6
2.9
02400023
3.1
3.5
02400032
4.7
5.1
10
02400041
5.8
6.2
10
03400056
8.3
8.7
10
10
03400073
10.2
12.2
16
16
03400094
13.1
14.8
20
04400135
14.0
16.3
20
20
04400170
18.5
20.7
25
25
NOTE