52
Unidrive M400 User Guide
Issue Number: 2
N
Any signal cables which are carried inside the motor cable (i.e. motor thermistor, motor brake) will pick up large pulse currents via the cable
capacitance. The shield of these signal cables must be connected to ground close to the point of exit of the motor cable, to avoid this noise current
spreading through the control system.
N
The SAFE TORQUE OFF drive enable terminals are positive logic input only (see Figure 4-30 on page 52).
Figure 4-29 Default terminal functions
Figure 4-30 Safe Torque Off inputs
Ensure the logic sense is correct for the control circuit to be used. Incorrect logic sense could cause the motor to be started unexpectedly.
Positive logic is the default state for the drive.
WARNING
NOTE
NOTE
Frequency
Torque (active current)
Analog
frequency
reference 1
Analog
frequency
reference 2
4
5
7
6
0V common
1
2
3
17
0V common
+10 V
41
42
Relay
(over-voltage
category II)
Drive ok/healthy
12
13
At zero frequency
Run forward
Jog forward
select
Run reverse
Analog input 1/
input 2 select
9
11
+24 V
+24 V
10
14
15
16
8
1
17
41 42
31
33
32
34
STO
Channel 1
STO
Channel 2
STO Input 1
0 V
STO1
0 V
STO2
STO Input 2