208
Unidrive M702 User Guide
Issue Number: 3
Parameter
Range( )
Default( )
Type
OL
RFC-A / S
OL
RFC-A
RFC-S
14.001
PID1 Output
±100.00 %
RO
Num
ND
NC
PT
14.002
PID1 Feed-forwards Reference Source
0.000 to 59.999
0.000
RW
Num
PT
US
14.003
PID1 Reference Source
0.000 to 59.999
0.000
RW
Num
PT
US
14.004
PID1 Feedback Source
0.000 to 59.999
0.000
RW
Num
PT
US
14.005
PID1 Reference Invert
Off (0) or On (1)
Off (0)
RW
Bit
US
14.006
PID1 Feedback Invert
Off (0) or On (1)
Off (0)
RW
Bit
US
14.007
PID1 Reference Slew Rate
0.0 to 3200.0 s
0.0 s
RW
Num
US
14.008
PID1 Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
14.009
PID1 Enable Source 1
0.000 to 59.999
0.000
RW
Num
PT
US
14.010
PID1 Proportional Gain
0.000 to 4.000
1.000
RW
Num
US
14.011
PID1 Integral Gain
0.000 to 4.000
0.500
RW
Num
US
14.012
PID1 Differential Gain
0.000 to 4.000
0.000
RW
Num
US
14.013
PID1 Output Upper Limit
0.00 to 100.00 %
100.00 %
RW
Num
US
14.014
PID1 Output Lower Limit
±100.00 %
-100.00 %
RW
Num
US
14.015
PID1 Output Scaling
0.000 to 4.000
1.000
RW
Num
US
14.016
PID1 Destination
0.000 to 59.999
0.000
RW
Num
DE
PT
US
14.017
PID1 Integral Hold
Off (0) or On (1)
Off (0)
RW
Bit
14.018
PID1 Symmetrical Limit Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
14.019
PID1 Feed-forwards Reference
±100.00 %
RO
Num
ND
NC
PT
14.020
PID1 Reference
±100.00 %
RO
Num
ND
NC
PT
14.021
PID1 Feedback
±100.00 %
RO
Num
ND
NC
PT
14.022
PID1 Error
±100.00 %
RO
Num
ND
NC
PT
14.023
PID1 Reference Scaling
0.000 to 4.000
1.000
RW
Num
US
14.024
PID1 Feedback Scaling
0.000 to 4.000
1.000
RW
Num
US
14.025
PID1 Digital Reference
±100.00 %
0.00 %
RW
Num
US
14.026
PID1 Digital Feedback
±100.00 %
0.00 %
RW
Num
US
14.027
PID1 Enable Source 2
0.000 to 59.999
0.000
RW
Num
PT
US
14.028
PID1 Pre-sleep Boost Level
0.00 to 100.00 %
0.00 %
RW
Num
US
14.029
PID1 Maximum Boost Time
0.0 to 250.0 s
0.0 s
RW
Num
US
14.030
PID1 Pre-sleep Boost Level Enable
Off (0) or On (1)
RO
Bit
ND
NC
PT
14.031
PID2 Output
±100.00 %
RO
Num
ND
NC
PT
14.032
PID2 Feed-forwards Reference Source
0.000 to 59.999
0.000
RW
Num
PT
US
14.033
PID2 Reference Source
0.000 to 59.999
0.000
RW
Num
PT
US
14.034
PID2 Feedback Source
0.000 to 59.999
0.000
RW
Num
PT
US
14.035
PID2 Reference Invert
Off (0) or On (1)
Off (0)
RW
Bit
US
14.036
PID2 Feedback Invert
Off (0) or On (1)
Off (0)
RW
Bit
US
14.037
PID2 Reference Slew Rate Limit
0.0 to 3200.0 s
0.0 s
RW
Num
US
14.038
PID2 Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
14.039
PID2 Enable Source 1
0.000 to 59.999
0.000
RW
Num
PT
US
14.040
PID2 Proportional Gain
0.000 to 4.000
1.000
RW
Num
US
14.041
PID2 Integral Gain
0.000 to 4.000
0.500
RW
Num
US
14.042
PID2 Differential Gain
0.000 to 4.000
0.000
RW
Num
US
14.043
PID2 Output Upper Limit
0.00 to 100.00 %
100.00 %
RW
Num
US
14.044
PID2 Output Lower Limit
±100.00 %
-100.00 %
RW
Num
US
14.045
PID2 Output Scaling
0.000 to 4.000
1.000
RW
Num
US
14.046
PID2 Destination
0.000 to 59.999
0.000
RW
Num
DE
PT
US
14.047
PID2 Integral Hold
Off (0) or On (1)
Off (0)
RW
Bit
14.048
PID2 Symmetrical Limit Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
14.049
PID2 Feed-forwards Reference
±100.00 %
RO
Num
ND
NC
PT
14.050
PID2 Reference
±100.00 %
RO
Num
ND
NC
PT
14.051
PID2 Feedback
±100.00 %
RO
Num
ND
NC
PT
14.052
PID2 Error
±100.00 %
RO
Num
ND
NC
PT
14.053
PID2 Reference Scaling
0.000 to 4.000
1.000
RW
Num
US
14.054
PID2 Feedback Scaling
0.000 to 4.000
1.000
RW
Num
US
14.055
PID2 Digital Reference
±100.00 %
0.00 %
RW
Num
US
14.056
PID2 Digital Feedback
±100.00 %
0.00 %
RW
Num
US
14.057
PID2 Enable Source 2
0.000 to 59.999
0.000
RW
Num
PT
US
14.058
PID1 Feedback Output Scaling
0.000 to 4.000
1.000
RW
Num
US