Issue Number: 10 www.controltechniques.com
Defines the current level used during DC injection braking as a percentage of motor rated current as defined by Pr
5.07
.
Defines the time of injection braking during phase 1 with stopping modes 3 and 4 (see Pr
on page 135) for injection braking stop.
When this bit is set the drive remains active even when the run command has been removed and the motor has reached standstill. The drive goes to
the 'StoP' state instead of the 'rdy' state.
Pr
6.08
may be changed by the brake control in menu 12.
6.06
Injection braking level
Drive modes
Open-loop
Coding
Bit
SP
FI
DE
TE VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
1
Range
Open-loop
0 to 150.0 %
Default
Open-loop
100.0 %
Update rate
Background read
6.07
Injection braking time
Drive modes
Open-loop
Coding
Bit
SP
FI
DE
TE VM DP
ND
RA NC NV
PT
US RW BU
PS
1
1
1
1
Range
Open-loop
0.0 to 25.0 s
Default
Open-loop
1.0
Update rate
Background read
6.08
Hold zero speed
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE
TE VM DP
ND
RA NC NV
PT
US RW BU
PS
1
1
1
Default
Open-loop, Closed-loop vector
Servo
0
1
Update rate
4ms read