Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
Menu 6
Unidrive SP Advanced User Guide
149
Issue Number: 10 www.controltechniques.com
When a drive with an internal rectifier is used this parameter should be left at zero. For a drive with an active external rectifier (used to control DC Bus
charging) this parameter should be the destination of the output of a variable selector set up for external rectifier monitoring. This allows the
monitoring block to prevent the drive from leaving the main loss ride through mode until the rectifier is fully active and phased forwards. If this feature
is not used the mains loss ride through mode ends as soon as the DC Bus voltage is above the mains loss detection level. The rectifier may still be
phasing forwards and the application of load at this point may cause the DC Bus voltage to fall back below the mains loss detection level again.
6.51
External rectifier not active
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE
TE
VM
DP
ND RA NC NV PT US RW BU PS
1
1
Default
Open-loop,Closed-loop vector, Servo, Regen
0
Update rate
1ms read