Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
Menu 14
Unidrive SP Advanced User Guide
249
Issue Number: 10 www.controltechniques.com
To enable the PID controller the drive must be OK/healthy (Pr
10.01
= 1) and the PID enable (Pr
14.08
) must be one. If the option enable source
(Pr
14.09
) is 00.00 or routed to a non-existent parameter the PID controller is still enabled provided Pr
10.01
= 1 and Pr
14.08
= 1. If the optional
enable source (Pr
14.09
) is routed to an existing parameter the source parameter must be one before the PID controller can be enabled. If the PID
controller is disabled the output is zero and the integrator is set to zero.
14.08
PID enable
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo,
Regen
0
Update rate
4ms read
14.09
PID optional enable source
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
2
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
Pr
0.00
to Pr
21.51
Default
Open-loop, Closed-loop vector, Servo,
Regen
Pr
0.00
Update rate
Read on reset
14.10
PID P gain
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
3
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0.000 to 4.000
Default
Open-loop, Closed-loop vector, Servo,
Regen
1.000
Update rate
Background read
14.11
PID I gain
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
3
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0.000 to 4.000
Default
Open-loop, Closed-loop vector, Servo,
Regen
0.500
Update rate
Background read
14.12
PID D gain
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
3
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0.000 to 4.000
Default
Open-loop, Closed-loop vector, Servo,
Regen
0.000
Update rate
Background read