Menus 15 to 17
SM-I/O Plus
Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
296
Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
The error status is provided so that the only one option error trip is required for each Solutions Module slot. If an error occurs, the reason for the error
is written to this parameter and the drive may produce a ‘SLx.Er’ trip, where x is the slot number. A value of zero indicates that the Solutions Module
has not detected an error, a non-zero value indicates that an error has been detected. (See Table 5-16 on page 289 for the meaning of the values in
this parameter). When the drive is reset, this parameter is cleared for the relevant Solutions Module.
This Solutions Module includes a temperature monitoring circuit. If the PCB temperature exceeds 90
°
C, the drive fan is forced to operate at full speed
(for a minimum of 10s). If the temperature falls below 90
°
C, the fan can operate normally again. If the PCB temperature exceeds 100
°
C, the drive is
tripped and the error status is set to 74.
x.50
Solutions Module error status
RO
Uni
NC
PT
Ú
0 to 255
Ö
Update rate: Background read