The menu for the relevant slot appears for the new Solutions Module category with the default parameter values for the new category.
When no Solutions Module is installed in the relevant slot this parameter is zero. When a Solutions Module is installed this parameter displays the
identification code.
204: SM-I/O PELV
The new parameter values are not stored in the drive EEPROM until the user performs a parameter save by setting Pr
xx.00
to 1000 (or 1001 in the
case of solely using the 24V back-up power supply) and pressing the stop/reset button. When parameters are saved by the user in the drive
EEPROM, the option code of the currently installed Solutions Module is saved in the drive EEPROM. If the drive is subsequently powered-up with a
different Solutions Module installed, or no Solutions Module is installed when one was previously installed, the drive will trip on SLx.dF or SLx.nF.
This module contains two processors, and thus two software versions. Pr
x.02
shows the version number of the main module processor. Pr
x.51
,
which is normally used to give a sub-version number, shows the software version in the slave processor, which operates on the PELV side of the
isolation barrier.
These parameters indicate the input and output states of the terminals.
The performance of the freeze input is highly dependant upon the quality of the signal driving it. If negative edge triggering is used then care should
be taken to ensure that the input is actively pulled low via low impedance. If positive edge triggering is used then care should be taken to ensure that
the input is actively pulled high, or pulled high via a suitably low pull-up resistance
The status of the PELV user power supply is shown in this parameter.
These parameters indicate the input and output states of the terminals.
x.01
Solutions Module ID code
RO
Uni
PT
US
Ú
0 to 599
Ö
Update rate: Write on power-up
x.02
Solutions Module main software version
RO
Uni
NC
PT
Ú
00.00 to 99.99
Ö
Update rate: Write on power-up
x.03
T5 digital I/O 3 state
x.04
T6 digital I/O 4 state
x.05
T7 digital input 5 state/freeze input
RO
Bit
NC
PT
Ú
OFF (0) or On (1)
Ö
Update rate: 4ms write
x.06
PELV user power supply state
RO
Bit
NC
PT
Ú
OFF (0) or On (1)
Ö
Update rate: 4ms write
x.07
Relay 1 state
x.08
Relay 2 state
x.09
T3 digital I/O 1 state
x.10
T4 digital I/O 2 state
RO
Bit
NC
PT
Ú
OFF (0) or On (1)
Ö
Update rate: 4ms write