Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
Menu 21
Unidrive SP Advanced User Guide
363
Issue Number: 10 www.controltechniques.com
0, drv
: Drive encoder
The position feedback from the encoder connected to the drive itself is used to derive the speed feedback for the speed controller and to calculate the
motor rotor flux position.
1, Slot1
: Solutions Module in slot 1
The position feedback from the Solutions Module in Solutions Module slot 1 is used to derive the speed feedback for the speed controller and to
calculate the motor rotor flux position. If a position feedback category Solutions Module is not installed in slot 1 the drive produces an EnC9 trip.
2, Slot2
: Solutions Module in slot 2
3, Slot3
: Solutions Module in slot 3
21.21
Speed feedback selector
Drive modes
Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
Range
Closed-loop vector, Servo
0 to 3
Default
Closed-loop vector, Servo
0
Normal motor
parameter
Closed-loop vector, Servo
Pr
3.26
Update rate
Background read
21.22
Current controller Kp gain
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0 to 30,000
Default
Drive voltage rating:
Open-loop,
Closed-loop vector, Servo
Regen
200V 400V 575V 690V
20 20 20 20
75 150 180 215
45 90 110 130
Normal
parameter
Open-loop, Closed-loop vector, Servo,
Regen
Pr
4.13
Update rate
Background read
21.23
Current controller Ki gain
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0 to 30,000
Default
Drive voltage rating:
Open-loop,
Closed-loop vector, Servo, Regen
200V 400V 575V 690V
40 40 40 40
1,000 2,000 2,400 3,000
Normal
parameter
Open-loop, Closed-loop vector, Servo,
Regen
Pr
4.14
Update rate
Background read
21.24
Stator inductance (L
s
)
Drive modes
Closed-loop vector
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
2
1
1
1
1
Range
Closed-loop vector
0.00 to 5,000.00 mH
Default
Closed-loop vector
0.00
Normal
parameter
Closed-loop vector
Pr
5.25
Update rate
Background read
Summary of Contents for unidrive sp
Page 419: ......
Page 420: ...0471 0002 10 ...