11 – 3
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Alarm Message
Cause(s)
Notes
(A020) Alarm: Blower 1 - High
Discharge Temperature
Blower 1 Discharge Temperature
exceeds "Discharge Temperature"
High Alarm Setpoint
(A021) Alarm: Blower 1 - High
Discharge Pressure
Blower 1 Discharge Pressure exceeds
"Discharge Pressure" High Alarm
Setpoint
(A022) Alarm: Blower 1 - Low
Suction Pressure
Blower 1 Suction Pressure falls
below "Suction Pressure" Low Alarm
Setpoint
(A023) Alarm: Blower 1 - High Phase
A Temperature
Phase A Motor Winding
Temperature exceeds Motor
Winding Temperature High Alarm
Setpoint
Active if Displaying Motor Winding
Temperatures
(A024) Alarm: Blower 1 - High Phase
B Temperature
Phase B Motor Winding Temperature
exceeds Motor Winding
Temperature High Alarm Setpoint
Active if Displaying Motor Winding
Temperatures
(A025) Alarm: Blower 1 - High Phase
C Temperature
Phase C Motor Winding Temperature
exceeds Motor Winding
Temperature High Alarm Setpoint
Active if Displaying Motor Winding
Temperatures
(A026) Alarm: Blower 1 - High ODE
Bearing Temperature
Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Alarm Setpoint
Active if Displaying Motor Bearing
Temperatures
(A027) Alarm: Blower 1 - High DE
Bearing Temperature
Opposite Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Alarm Setpoint
Active if Displaying Motor Bearing
Temperatures
(A028) Alarm: Blower 1 - High Motor
Amps
Blower 1 Motor Amps exceeds
"Motor Amps" High Alarm Setpoint
(A029) Alarm: Blower 1 - VFD Speed
Reference Fault
Blower 1 Actual Speed is not within
1% of commanded speed.
(A030) Alarm: Blower 1 - Oil Cooler
Fan Fault
Blower 1 Oil Cooler Fan is command-
ed to run, running con
fi
rmation is
not received.
Active if an air-cooled oil cooler is
installed.
(A031) Alarm:
(A032) Alarm:
(A033) Alarm:
(A034) Alarm:
(A035) Alarm:
(A036) Alarm:
(A037) Alarm:
(A038) Alarm:
(A039) Alarm:
(A040) Alarm: Blower 2 - High
Discharge Temperature
Blower 2 Discharge Temperature
exceeds "Discharge Temperature"
High Alarm Setpoint
(A041) Alarm: Blower 2 - High
Discharge Pressure
Blower 2 Discharge Pressure exceeds
"Discharge Pressure" High Alarm
Setpoint
Summary of Contents for Vilter PLC
Page 1: ...Blower Package PLC Operation manual ...
Page 2: ......
Page 10: ...Blank TOC Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 18: ...1 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 30: ...3 2 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 34: ...4 4 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 42: ...5 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 48: ...6 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 54: ...7 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 62: ...9 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 68: ...10 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 117: ......