11 – 4
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Alarm Message
Cause(s)
Notes
(A042) Alarm: Blower 2 - Low
Suction Pressure
Blower 2 Suction Pressure falls
below "Suction Pressure" Low Alarm
Setpoint
(A043) Alarm: Blower 2 - High Phase
A Temperature
Phase A Motor Winding
Temperature exceeds Motor
Winding Temperature High Alarm
Setpoint
Active if Displaying Motor Winding
Temperatures
(A044) Alarm: Blower 2 - High Phase
B Temperature
Phase B Motor Winding Temperature
exceeds Motor Winding
Temperature High Alarm Setpoint
Active if Displaying Motor Winding
Temperatures
(A045) Alarm: Blower 2 - High Phase
C Temperature
Phase C Motor Winding Temperature
exceeds Motor Winding
Temperature High Alarm Setpoint
Active if Displaying Motor Winding
Temperatures
(A046) Alarm: Blower 2 - High ODE
Bearing Temperature
Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Alarm Setpoint
Active if Displaying Motor Bearing
Temperatures
(A047) Alarm: Blower 2 - High DE
Bearing Temperature
Opposite Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Alarm Setpoint
Active if Displaying Motor Bearing
Temperatures
(A048) Alarm: Blower 2 - High Motor
Amps
Blower 2 Motor Amps exceeds
"Motor Amps" High Alarm Setpoint
(A049) Alarm: Blower 2 - VFD Speed
Reference Fault
Blower 2 Actual Speed is not within
1% of commanded speed.
(A050) Alarm: Blower 2 - Oil Cooler
Fan Fault
Blower 2 Oil Cooler Fan is command-
ed to run, running con
fi
rmation is
not received.
Active if an air-cooled oil cooler is
installed.
(A051) Alarm:
(A052) Alarm:
(A053) Alarm:
(A054) Alarm:
(A055) Alarm:
(A056) Alarm:
(A057) Alarm:
(A058) Alarm:
(A059) Alarm:
(A060) Alarm: Blower 3 - High
Discharge Temperature
Blower 3 Discharge Temperature
exceeds "Discharge Temperature"
High Alarm Setpoint
(A061) Alarm: Blower 3 - High
Discharge Pressure
Blower 3 Discharge Pressure exceeds
"Discharge Pressure" High Alarm
Setpoint
(A062) Alarm: Blower 3 - Low
Suction Pressure
Blower 3 Suction Pressure falls
below "Suction Pressure" Low Alarm
Setpoint
Summary of Contents for Vilter PLC
Page 1: ...Blower Package PLC Operation manual ...
Page 2: ......
Page 10: ...Blank TOC Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 18: ...1 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 30: ...3 2 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 34: ...4 4 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 42: ...5 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 48: ...6 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 54: ...7 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 62: ...9 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 68: ...10 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 117: ......