11 – 9
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Trip Message
Cause(s)
Notes
(T001) Trip: MCR Not Energized/E-
Stop Active
Emergency Stop Button on PLC Panel
Pressed, Loss of Power, External
Emergency Stop Device Tripped
(T002) Trip: PLC to Central Comms
Faulted
Loss of Communication with DCS/
Central - Settable Communications
Watchdog Timer Expired. (Action on
Comm Failure = Trip)
Watchdog Active if Control by
Communications is selected
(T003) Trip:
(T004) Trip: Setpoint out of Range -
See Menu Screen
(T005) Trip: Invalid Blower
Con
fi
guration
Blower Con
fi
guration or Suction/
Discharge Pressure Source is invalid.
See Blower Con
fi
guration Screen.
(T006) Trip:
(T007) Trip: Faulted I/O Module
Connection or Module Type
(T008) Trip:
(T009) Trip:
(T010) Trip: Low Suction Header
Pressure
Suction Header Pressure drops
below "Suction Pressure" Low Trip
Setpoint
Active if monitoring Suction Header
Pressure
(T011) Trip: High Discharge Header
Pressure
Suction Header Pressure rises above
"Discharge Pressure" High Trip
Setpoint
Active if monitoring Discharge
Header Pressure
(T012) Trip:
(T013) Trip:
(T014) Trip:
(T015) Trip: User De
fi
ned Trip 1
User de
fi
ned Trip 1
Message De
fi
ned in "Device Names"
Screens
(T016) Trip: User De
fi
ned Trip 2
User de
fi
ned Trip 2
Message De
fi
ned in "Device Names"
Screens
(T017) Trip: User De
fi
ned Trip 3
User de
fi
ned Trip 3
Message De
fi
ned in "Device Names"
Screens
(T018) Trip: User De
fi
ned Trip 4
User de
fi
ned Trip 4
Message De
fi
ned in "Device Names"
Screens
(T019) Trip: User De
fi
ned Trip 5
User de
fi
ned Trip 5
Message De
fi
ned in "Device Names"
Screens
(T020) Trip: Blower 1 - High
Discharge Temperature
Blower 1 Discharge Temperature
exceeds "Discharge Temperature"
High Trip Setpoint
Trip Listing
Table 11-2. Trip Listing
Blower will shutdown if active.
Summary of Contents for Vilter PLC
Page 1: ...Blower Package PLC Operation manual ...
Page 2: ......
Page 10: ...Blank TOC Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 18: ...1 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 30: ...3 2 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 34: ...4 4 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 42: ...5 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 48: ...6 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 54: ...7 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 62: ...9 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 68: ...10 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 117: ......