14 – 6
Section 14
•
Slide Calibration
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Command Shaft Rotation
The following table describes the rotation direction required by the actuator. Every optical actuator has the ability to
be wired to rotate in either direction. Energizing the blue actuator wire results in a CCW rotation and energizing the
brown wire results in a CW rotation, see Table 14-1. Command Shaft Rotation Required By Actuator.
Table 14-1. Command Shaft Rotation Required By Actuator
Compressor
Model
Command Shaft Rotation
Number of Turns / Rotation Angle / Slide Travel
Capacity
Volume
Capacity
Volume
INC
DEC
INC
DEC
Turns
Angle Travel Turns Angle
Travel
VSR 111
CW
CCW
CW
CCW
0.91
328
3.568”
0.52
187
2.045”
VSR 151
CW
CCW
CW
CCW
0.91
328
3.568”
0.52
187
2.045”
VSR 221
CW
CCW
CW
CCW
0.91
328
3.568”
0.52
187
2.045”
VSR 301
CW
CCW
CW
CCW
0.91
328
3.568”
0.52
187
2.045”
VSS 451
CW
CCW
CW
CCW
0.91
328
3.568”
0.52
187
2.045”
VSS 601
CW
CCW
CW
CCW
0.91
328
3.568”
0.52
187
2.045”
VSS 751
CCW
CW
CCW
CW
1.09
392
4.283”
0.63
227
2.473”
VSS 901
CCW
CW
CCW
CW
1.09
392
4.283”
0.63
227
2.473”
VSS 1051
CCW
CW
CCW
CW
1.22
439
4.777”
0.74
266
2.889”
VSS 1201
CCW
CW
CCW
CW
1.22
439
4.777”
0.74
266
2.889”
VSS 1301
CCW
CW
CCW
CW
1.22
439
4.777”
0.74
266
2.889”
VSS 1501
CCW
CW
CCW
CW
1.36
490
5.325”
0.82
295
3.200”
VSS 1551
CCW
CW
CCW
CW
1.48
533
5.823”
0.87
313
3.433”
VSS 1801
CCW
CW
CCW
CW
1.36
490
5.325”
0.82
295
3.200”
VSS 1851
CCW
CW
CCW
CW
1.48
533
5.823”
0.87
313
3.433”
VSS 2101
CCW
CW
CCW
CW
1.48
533
5.823”
0.87
313
3.433”
VSS 2401
CCW
CW
CCW
CW
1.80
648
7.072”
1.36
490
5.341”
VSS 2601
CCW
CW
CCW
CW
1.80
648
7.072”
1.36
490
5.341”
VSS 2801
CCW
CW
CCW
CW
1.80
648
7.072”
1.36
490
5.341”
VSS 3001
CCW
CW
CCW
CW
1.80
648
7.072”
1.36
490
5.341”
VSM 71
CW
CCW
CW
CCW
0.80
288
3.141”
0.45
162
1.767”
VSM 91
CW
CCW
CW
CCW
0.80
288
3.141”
0.45
162
1.767”
VSM 101
CW
CCW
CW
CCW
0.80
288
3.141” 0.45
162
1.767”
VSM 151
CW
CCW
CW
CCW
0.80
288
3.141”
0.45
162
1.767”
VSM 181
CW
CCW
CW
CCW
0.80
288
3.141”
0.45
162
1.767”
VSM 201
CW
CCW
CW
CCW
0.80
288
3.141”
0.45
162
1.767”
VSM 301
CW
CCW
CW
CCW
0.80
288
3.141”
0.45
162
1.767”
VSM 361
CW
CCW
CW
CCW
0.80
288
3.141”
0.45
162
1.767”
VSM 401
CW
CCW
CW
CCW
0.80
288
3.141”
0.45
162
1.767”
VSM 501
CCW
CW
CCW
CW
0.91
328
3.568”
0.52
187
2.045”
VSM 601
CCW
CW
CCW
CW
0.91
328
3.568”
0.52
187
2.045”
VSM 701
CCW
CW
CCW
CW
0.91
328
3.568”
0.52
187
2.045”
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......