19 – 4
Section 19
•
Configuration
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Anti-Recycle
Anti-Recycle defines the method of motor protection
due to repeated motor starts. The operator has 3 choices
of protection. “Hot starts” allow only a certain number
of starts per hour before setting the anti-recycle timer to
one hour . The number of starts is set in the timer page.
“Accumulative” immediately adds time to the anti-recy-
cle timer once the compressor is started and the time
can be set in the timers screen. “True anti-recycle” adds
to the anti-recycle timer once the compressor is shut-
down. The motor of the compressor cannot be restarted
if there is anti-recycle time left, and the operator can
view this time on the top left corner of the main screen.
Restart On Power Failure
This feature of the Vission 20/20 offers the ability to de-
fine how the Vission 20/20 will handle a power failure.
This can also be useful to allow a system controller to
regain control of the Vission panel without the need of
operator intervention.
Always:
• When selected, initiates a start after the panel pow-
ers back up after a power failure, but only if the com-
pressor was running before the power failure and
starts the compressor in Auto mode.
Never:
• When selected, prevents any automatic action once
the panel powers back up after a power failure.
Timed:
• When selected, initiates a start after the panel pow-
ers back up after a power failure and the operator-set
timer runs out. When there are multiple compressors
in a larger system, it is recommended for the opera-
tor to give each compressor a different start time. A
restart will only occur if the compressor was running
before the power failure and starts the compressor in
Auto mode.
Remote Lock Off:
• When selected, turns the remote lock out off when
the panel powers up. Select this option if the opera-
tor wishes a system controller to regain control of the
Vission 20/20 without human interference.
Boot in Remote (Direct I/O):
• When selected, places the panel into Remote mode
when the panel powers up. Select this option when
under Direct I/O control and the system controller is
to gain control of the Vission 20/20 without human
interference.
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......