Section 2
•
Installation Recommendations
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Grounding
• Continuous grounds must be run from the util-
ity ground to the Vission 20/20, see Figure 2-3.
Grounding.
• Grounds must be copper or aluminum wire.
• Never use conduit grounds.
Mixing Voltages
• Separate different voltages from each other and sep-
arate AC from DC, see Figure 2-4.
Figure 2-4. Mixed Voltage Wiring
• Each voltage level must be run in separate conduit:
• If your installation site has wireways or conduit trays,
dividers must be installed between the different
voltages.
DC signals
• If your installation site has wire-ways or conduit trays,
dividers must be installed between the different
voltages.
Figure 2-3. Ground Wiring
• 460 VAC
• 230 VAC
• 120 VAC
• 24 VAC
• DC Signals