B - 24
Appendix B
•
Vission 20/20 Application Procedures
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Test 1
The first test measured the noise on the active net
-
work WITHOUT the ILinx™485OPDRI-PH isolator in-
stalled in the network. The USB/RS485 convertor was
wired directly to the Vission 20/20 RS485 serial port.
The following screen capture from the scope shows the
amount of noise on the network signals, see Figure B-13.
Figure B-13. Network Noise
Test 2
The second test measured the noise on the active net-
work with the ILinx™485OPDRI-PH isolator installed
in the network. The following screen capture (Figure
B-14) from the scope shows the amount of noise on the
network signals.
The noise on the signal lines has been significantly re
-
duced with the addition of the ILinx™485OPDRI-PH iso-
lator installed in the network.
Figure B-14. Network Noise with Phoenix Contact PSM-ME Isolator
NOTE
The ILinx™485OPDRI-PH was
powered from the +24vDC
supply from the Vission 20/20
panel in this test, to measure
the benefits of the isolator
on an RS485 serial network
running Modbus RTU protocol.
To order this isolator, please use
Vilter part number 3485C1
.