B - 27
Appendix B
•
Vission 20/20 Application Procedures
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Step 3: Selection and Naming of Auxiliary Analog
Inputs used for Level Control
Navigate to page 6 of the Configuration screen and se
-
lect the analog inputs(s) that will be used for sensing the
4-20mA signal from the vessel(s) level probe(s). Also
provide a name for the analog input(s). You’ll need to
reference your wiring diagram to determine which ana-
log inputs need to be enabled.
In the example in Figure B-17, Auxiliary #5 Analog Input
was renamed to “Chiller Level 4,20 Input” and Auxiliary
#6 Analog Input was renamed to “Condenser Level 4,20
Input”. Referencing the wiring diagram, please note that
Aux #5 Analog Input corresponds to Channel #21 on the
wiring diagram and Aux #6 Analog Input corresponds to
Channel #22 on the wiring diagram.
After steps 1, 2 and 3 have been completed, then press
the APPLY button and then press the CLOSE button to
exit the Configuration screen.
Continue to step 4.
Figure B-17. Enabling and Naming Analog Inputs (Configuration Screen – Page 6)