3 – 3
Section 3
•
Hardware Architecture
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Table 3-1. Digital I/O (1 of 2)
Board
I/O #
Description
Type
1
1
Compressor Start
OUTPUT
1
2
Oil Pump Start
OUTPUT
1
3
Capacity Increase
OUTPUT
1
4
Capacity Decrease
OUTPUT
1
5
Volume Increase
OUTPUT
1
6
Volume Decrease
OUTPUT
1
7
Oil Separator Heater
OUTPUT
1
8
Trip indicator (ON=Normal)
OUTPUT
2
9
Slide Valve Set point #1 (Economizer Port #1)
OUTPUT
2
10
Slide Valve Set point #2 (Hot Gas Bypass)
OUTPUT
2
11
Alarm (ON=Normal)
OUTPUT
2
12
Economizer Port #2
OUTPUT
2
13
Liquid Injection #1
OUTPUT
2
14
Liquid Injection #2
OUTPUT
2
15
Remote Enabled
OUTPUT
2
16
Shunt Trip
OUTPUT
3
17
Comp Motor Starter Auxiliary Contact
INPUT
3
18
High Level Shutdown
INPUT
3
19
Oil Level Float Switch #1
INPUT
3
20
Oil Level Float Switch #2
INPUT
3
21
Remote Setpoint #1/#2 Selection
INPUT
3
22
Remote Start/Stop
INPUT
3
23
Remote Capacity Increase
INPUT
3
24
Remote Capacity Decrease
INPUT
4
25
Condenser / Remote Oil Cooler Step #1
OUTPUT
4
26
Condenser / Remote Oil Cooler Step #2
OUTPUT
4
27
Condenser / Remote Oil Cooler Step #3
OUTPUT
4
28
Condenser / Remote Oil Cooler Step #4
OUTPUT
4
29
Auxiliary Input #1
INPUT
4
30
Auxiliary Input #2
INPUT
4
31
Auxiliary Input #3
INPUT
4
32
Auxiliary Input #4
INPUT
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......