C - 29
Appendix C
•
Remote Control and Monitoring of Vission 20/20 Panel
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
COMMUNICATION PORT SETUP
(Reference the “Communication” section of Figure C-14)
For Serial Port Modbus RTU Monitoring:
• Check the “Serial” box inside the
“Communications” section.
•
Configure serial port settings (baud rate, #
data bits, # stop bits, parity) and panel ID num-
ber (which is “node” number for Modbus RTU.)
For Ethernet Monitoring:
• Check the “Ethernet” box inside the
“Communications” section.
•
Configure IP address and Subnet Mask.
• Select Protocol (Ethernet I/P or Modbus TCP/
IP)
Once the port is setup properly, communication can be
established. You will be able to read from and write to
registers. In Direct I/O mode, you cannot write to reg-
isters in the Control Block region of Modbus registers
40500 through 40513.