D - 28
Appendix D
•
Vission 20/20 Communication Table
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Vilter
TM
Address
Ethernet
IP
Address
Modbus
Address
Command Name
Data
Type
Value
Mode
Lower
Range
Higher
Range
522
N72:31
41431
Step #2 VFD Enabled
INT
0 = Disabled, 1 =
Enabled
Read-Write
523
N72:32
41432
Step #3 VFD Enabled
INT
0 = Disabled, 1 =
Enabled
Read-Write
524
N72:33
41433
Step #4 VFD Enabled
INT
0 = Disabled, 1 =
Enabled
Read-Write
525
N72:34
41434
Step #5 VFD Enabled
INT
0 = Disabled, 1 =
Enabled
Read-Write
526
N72:35
41435
Step#1 Step Delay
(seconds)
INT
Read-Write 5
60
527
N72:36
41436
Step#2 Step Delay
(seconds)
INT
Read-Write 5
60
528
N72:37
41437
Step#3 Step Delay
(seconds)
INT
Read-Write 5
60
529
N72:38
41438
Step#4 Step Delay
(seconds)
INT
Read-Write 5
60
530
N72:39
41439
Step#5 Step Delay
(seconds)
INT
Read-Write 5
60
531
N72:40
41440
Step #1 Low Speed
Fan
ENUM
"0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
532
N72:41
41441
Step #2 Low Speed
Fan
ENUM
"0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
533
N72:42
41442
Step #3 Low Speed
Fan
ENUM
"0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
534
N72:43
41443
Step #4 Low Speed
Fan
ENUM
"0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
535
N72:44
41444
Step #5 Low Speed
Fan
ENUM
"0 = None
1 = Out # 1
2 = Out # 2
3 = Out # 3
4 = Out # 4"
Read
536
N72:45
41445
VFD Gain (P)
F-INT
Read-Write 0.0
10.0
537
N72:46
41446
VFD Reset (I)
F-INT
Read-Write 0.0
10.0
538
N72:47
41447
VFD Rate (D)
F-INT
Read-Write 0.0
10.0
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......