D - 34
Appendix D
•
Vission 20/20 Communication Table
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
• Statuses: Trip Status Word(s) – currently 54 trips, so all Trip Status Words 1, 2, 3 and 4 are used, with each position
indicating an trip:
Word 1
Word 2
Bit 0 = Low Suction Pressure Warning
Bit 0 = High Process Pressure Warning
Bit 1 = High Discharge Pressure Warning
Bit 1 = Unused
Bit 2 = Low Process Temp. Warning
Bit 2 = Unused
Bit 3 = Low Suction Temp. Warning
Bit 3 = Unused
Bit 4 = High Discharge Temp. Warning
Bit 4 = Unused
Bit 5 = Low Oil Separator Temp. Warning
Bit 5 = Unused
Bit 6 = High Oil Injection Temp. Warning
Bit 6 = Unused
Bit 7 = High Superheat Temp Warning
Bit 7 = Unused
Bit 8 = High Filter Differential Warning
Bit 8 = Unused
Bit 9 = High Level Shutdown Warning
Bit 9 = Unused
Bit 10 = Low Discharge Pressure Warning
Bit 10 = Unused
Bit 11 = Low Discharge Temp. Warning
Bit 11 = Unused
Bit 12 = Low Oil Injection Temp. Warning
Bit 12 = Unused
Bit 13 = Low Oil Filter In Pressure Warning
Bit 13 = Unused
Bit 14 = Low Oil Filter Out Pressure Warning
Bit 14 = Unused
Bit 15 = Low Process Pressure Warning
Bit 15 = Unused
MSB
LSB
[Bit 15, Bit 14, Bit 13, ... Bit 3, Bit 2, Bit 1, Bit 0]
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......