3 – 12
Section 3
•
Hardware Architecture
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Analog Input Boards
The analog input board converts varying DC signals into
a signal that can interpreted by the Vission 20/20 pro-
gram. The signals are considered analog because the
input DC signal can vary from the minimum value to the
maximum value. See board layout, Figure 3-8.
Configuration Jumpers:
• Marked in the diagram below in Purple. The jumpers
allow the operator to configure the signal type and
range for incoming analog signals. For the correct
jumper setting for a giving application, see Table 3-4.
Analog Input Jumper Tables.
Voltage LEDs:
• Marked in the diagram below in Orange. These LEDs
indicate the correct voltage of both the 5V DC and
24V DC power sources.
Communication LEDs:
• Marked in the diagram below in Green. These LEDs
show the active communications between the digital
output board and the Vission 20/20 CPU board.
Address Dipswitches:
• Marked in the diagram below in Red. These dipswitch-
es are used to assign each board its address position.
The addresses are binary and therefore the address
of a digital output board will be address 6 (0110), 7
(0111), 8 (1000) or 9 (1001).
Figure 3-8. Analog Input Board Layout