4 – 2
Section 4
•
Main Screen
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 4-2. Top Status Bar
Top Status Bar
The standard view of the status bar shows three pieces
of information. From left to right , the bar shows the con-
trol method, the current run mode, and the difference
between the desired control setpoint and the actual val-
ue of the processes control value, see Figure 4-2.
The status bar also has an alternate function where it dis-
plays to the user any information that requires the user’s
attention or intervention. It accomplishes this by chang-
ing the status bar’s color and/or flashing additional infor
-
mation bars over the standard status bar view.
Standard Bar – blue:
• Indicates a condition where the compressor motor is
not running.
Standard Bar – green:
• Informs the operator that the compressor motor is
currently running.
Information Bars will flash their information over the top
of the status bar. The operator will see the status bar
and then one or more information bars in a repetitive
sequence.
Information Bar – blue:
• Shows various operational modes that are different
than normal running condition. An example of this
would be a load limit condition. The compressor is
not able to completely load due to some parameter
like high motor current and therefore the operator is
notified via this type of information bar.
Information bar – yellow
• This typically indicates an Alarm condition. Alarm
conditions do not stop the compressor but are meant
to alert the operator of conditions such that, if no cor-
rective action is taken, can result in a compressor trip.
Information bar – red
• Informs the operator that the compressor’s motor
was stopped due the condition listed in the informa-
tion bar. Compressor trips are designed to protect
the equipment and any personnel operating the
equipment.
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......