6 – 1
Section 6
•
Compressor Control
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 6-1. Compressor Control Screen - Suction Pressure Control
Overview
The compressor control screen is where an operator
can set the majority of the compressor settings. These
settings define how the compressor will operate and re
-
spond to changing loads. The compressor control screen
consists of several screens, but in order not to over-
whelm the operator with options, many of the screens
may not be visible.
NOTE
How the compressor is set up in the configuration
screen (Section 19) will determine what compressor
control pages are displayed. Additional setup
information can be found in Appendix B.
It is important to note that there isn’t one correct way to
set these parameters. Every application is different and
requires the operator to tune these settings to achieve
the best operation.
Suction Pressure Control, Process
Temperature Control, Process Pressure
Control and Discharge Pressure Control
The Vission 20/20 uses a pulse proportional control
method to control the compressor capacity slide valve
in order to maintain the control setpoint. The control
setpoint can either be the suction pressure control set-
point, process temperature control setpoint, process
pressure control setpoint or discharge pressure control
setpoint depending on what the operator has selected
as the control mode. For screens, see Figure 6-1, Figure
6-2, Figure 6-3 and Figure 6-5.
The proportional control uses the Interval Time Setpoint
to define the time that the algorithm waits to read the
current setpoint and calculate the error from the process
control setpoint. Based on the error from setpoint, the
algorithm calculates a pulse time in which the capacity
slide is moved in the direction of the error. The further
away the process variable is from the control setpoint,
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......