Compressor Control
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 6-13. Compressor Control Screen - Control Mode (SOI)
Solenoid should be wired to “Oil Pump Start” Digital
Output, see Figure 6-13.
SOI Solenoid Press Restart Ratio:
•
The On and Off setpoints define when the SOI sole
-
noid will Cycle On and Off depending on Discharge to
Suction Pressure Ratio.
SOI Solenoid ON Timer:
•
This setpoint defines the time interval for which the
SOI Solenoid is Forced ON when the compressor is
started or when the SOI Solenoid is Cycled On when
the compressor is running.
SOI Load Limit:
•
This setpoint defines the maximum value for the ca
-
pacity slide position when SOI Solenoid is ON.No Oil
Pump
Refer to Figure 6-14 for the No Oil Pump Control Setpoints.
When No Pump is selected in the Configuration Screen,
the Oil Pump digital Output is Forced OFF.
No Oil Pump Pressure Ratio:
•
This setpoint defines the load limit condition of No
Oil Pump when No Pump is selected in the configu
-
ration screen. This setpoint is monitored against
Pressure Ratio.
No Oil Pump Load Limit:
•
This setpoint defines the maximum value for the ca
-
pacity slide position when the Pressure Ratio drops
below the No Oil Pump Pressure Ratio Setpoint.