6 – 21
Section 6
•
Compressor Control
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Continuous VI
• If this method is selected then the volume slide valve
will be controlled according to the current volume
ratio.
Minimum VI
•
This setpoint defines the minimum slide position val
-
ue (0%) for volume slide valve. The default value for
Minimum VI is 2.2.
Maximum VI
•
This setpoint defines the maximum slide position
value (100%) for volume slide valve. The default value
for Maximum VI is 5.0.
Figure 6-19. Compressor Control Screen - Continuous VI (Twin Screw)
Deadband
•
This setpoint defines the deadband for the calcula
-
tion of the volume slide position. Volume will not
be changed till the Volume Ratio changes by this
amount. The default value for Deadband is 0.4.
Time Interval
•
This setpoint specifies the time interval after which
the volume ratio is calculated to determine the posi-
tion of the volume slide valve.