8 – 1
Section 8
•
Timers
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Overview
The timers screen allows the operator to view and adjust
timer settings associated with compressor operation.
There are different types of timers that the operator
should be aware of listed below. For Timer Screen Pages,
see Figures 8-1 and 8-2.
Changeover:
• The changeover timers will change from one type
control to another once the compressor has started
and then the timer has expired.
Bypass:
• The bypass timers prevent certain alarm and trip
checks from occurring until the compressor has
started and then the time has expired.
Delays:
• Delays require the condition to occur for the speci-
fied amount of time.
Timers:
• A general timer requiring the time to expire before
the listed event can occur.
Timer Setpoints
Capacity Increase Start Delay:
• At compressor startup, the capacity slide position is
held at minimum position for this time period. This is
to allow compressor and system conditions to stabi-
lize. After the timer expires, the slide is free to move
in accordance to the system demands.
Minimum Compressor Pre-lube Time:
• This is the length of time the oil pump will run, after
establishing Pre-lube Oil Pressure, to prime the oil cir-
cuit before starting the compressor.
Low Oil Pressure Safety Bypass:
• This is the length of time in which the normal Low
Figure 8-1. Timers Screen - Page 1
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......