4
DKRCI.PI.FT0.C4.02 / 520H5450
© Danfoss A/S (AC-MCI/MWA), 2012-12
Operating the manual opener on ICFE 20H solenoid valve module
Operating the manual opener on ICFE 25 solenoid module
To force open the solenoid by the manual stem turn it
counter clockwise
full way up. (Manual mode)
To operate the solenoid in automatic mode, turn the manual stem
clockwise
until the locking ring stops.
Do not force the spindle further. If the locking ring is damaged or removed the spindle will start to leak.
The valve cannot be forced closed by the manual stem.
ICFE 25-40 solenoid valve module
Locking ring
Turn spindle counter clockwise to open
Remove the cap on the side of the ICFE 20H
At 9 o’clock position the manual opener is disabled (not active)
To force the ICFE 20H solenoid to open use a 5 mm Allen key and turn it
clockwise
to 3 o’clock position.
Manual opener disabled
Position for forced open