14 – 8
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Section 14
•
Slide Calibration
Table 14-2. Slide Valve Troubleshooting Guide (2 of 2)
Problem
Reason
Solution
There is a rapid clicking noise when
the motor is operating. (Continued)
The position sensor’s EEPROM
memory has failed.
Replace the actuator.
There is a rapid clicking noise when
the motor is operating.
The photo-chopper is misaligned
with the slotted optocouplers.
Try to realign or replace the actuator.
The photo-chopper is positioned too
low on the motor shaft.
Adjust the photo-chopper so that
the fence extends further into the
optocoupler slots.
A motor bearing has failed.
Replace the actuator.
The motor operates in one direction
only.
There is a loose connection in the
screw terminal blocks.
Tighten.
There is a loose or dirty connection
in the yellow Turck cable.
Clean and tighten.
The position sensor has failed.
Replace the actuator.
There is a broken motor lead or
winding.
Replace the actuator.
The motor will not move in either
direction.
The thermal switch has tripped be-
cause the motor is overheated.
The motor will resume operation
when it cools. This could be caused
by a malfunctioning control panel.
Consult the factory.
Any of the reasons listed in “The mo-
tor operates in one direction only”.
See above.
The command shaft is jammed.
Free the command shaft.
Broken gears in the gear-motor.
Replace the actuator.
Blown relays or fuses.
Check and replace blown relays and/
or fuses.
The motor runs intermittently, sev-
eral minutes on, several minutes off.
Motor is overheating and the ther-
mal switch is tripping.
This could be caused by a malfunc-
tioning control panel. Consult the
factory.
The motor runs sporadically.
Bad thermal switch.
Replace the actuator.
Any of the reasons listed in “The mo-
tor will not move in either direction”.
See above.
The motor runs but output shaft will
not turn.
Stripped gears inside the gear rotor,
or the armature has come unpressed
from the armature shaft.
Replace the actuator.
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......