Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9
Digital Outputs
The digital outputs section of the Auxiliary I/O screen
allows an operator to con
fi
gure the auxiliary digital
outputs, see Figure 18-2. The digital output can be con-
fi
gured to activate (go High, 120vac) based on either a
digital input or a speci
fi
ed level on an analog input. Every
digital and analog input in the Vission 20/20 are made
available for controlling a digital output.
Analog Input:
• Selecting the Analog Input radio button
fi
lls the
Active Input drop-down box with all available analog
inputs. One of the analog inputs can then be selected
to control the digital outputs.
Digital Input:
• Selecting the Digital Input radio button
fi
lls the
Active Input drop-down box with all available digital
inputs. One of the digital inputs can then be selected
to control the digital outputs.
Run Always:
• Selecting this checkbox enables the function that
controls the digital output to operate only when the
compressor is running or runs all the time.
Analog Trigger:
• The analog trigger toggles the digital output based
on a speci
fi
ed value plus the speci
fi
ed differential
value.
• Analog Trigger value:
• This de
fi
nes the speci
fi
ed value in which the
output will toggle. This is an absolute value
and not based on units. For example, 100 could
mean temperature or pressure depending on
the type of input selected.
• N/O & N/C:
• Choosing the Normally Open (N/O) or
Normally Closed (N/C) radio buttons de
fi
nes
what the output will be above or below the trig-
ger value. In the N/O setting, the output will be
off (0vac) while the input value is below the trig-
ger value.
• Differential:
• This is the differential around the trigger val-
ue. For example, if a trigger value of 100 is en-
tered with a differential of 1, then as the value
increases to 101, the output will be triggered. If
the value decreases to 99, then the output will
be toggled in the opposite direction.
Digital Relay:
• The digital relay option is used to pass along the in-
formation from a digital input to another control de-
vice or to operate a peripheral device. This output can
be con
fi
gured to either re
fl
ect the selected input or
show the opposite value.
• Mirror:
• Selecting this option will produce a high out-
put when the selected input is High; and pro-
duce a low output when the selected input is
low.
• Invert:
• Selecting this option will produce a low out-
put when the selected input is high; and pro-
duce a High output when the selected input is
low.
Analog Inputs
The Analog inputs section of the auxiliary I/O screen al-
lows an operator to de
fi
ne the function of an instrument
connected to the Vission 20/20. For Auxiliary Analog
Inputs Screens, see Figure 18-3, 18-4 and 18-5. The ana-
log inputs can be con
fi
gured to simply monitor an input
for informational purposes or used as a control input for
the auxiliary digital and analog outputs. The analog in-
puts can also be con
fi
gured to alarm, trip, and inhibit on
speci
fi
ed values.
• Alarm / Trip:
• This drop-down box allows the operator to
select whether the analog input should gener-
ate an alarm, trip, or both when the input value
exceeds the limits entered into the alarm and
trip entry boxes.
• Inhibit:
• Selecting this checkbox will prevent a start if
the input value exceeds the alarm limit values.
• Low Alarm:
• This de
fi
nes the lower limit of the input value
that when exceeded will generate an alarm.
• High Alarm:
• This de
fi
nes the upper limit of the input value,
that when exceeded will generate an alarm.
• Low Trip:
• De
fi
nes the lower limit of the input value that
when exceeded will generate a trip.
Section 18
•
Auxiliary Input / Output
Summary of Contents for Vission 20/20
Page 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Page 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Page 257: ......